Updated:2024-04-01
Views:923
Online Service
The IMP range of level sensors feature a combined transducer and controller in one self-contained unit. All IMP units from Pulsar Measurement are non-contacting, accurate, and reliable level measurement units. The IMP level sensors do not come into contact with the process, therefore there is no need to shut down or interrupt operations. Featuring specially designed digital echo processing technology, the IMP level measurement units provide simple, accurate, and reliable level measurement on their onboard LCD displays.
The IMP I.S. level sensor is certified to ATEX standard EEx ia IIC T4 and IECEx, and is available with wetted parts in PVDF, making it ideal for measuring in corrosive or aggressive applications. Available in three measurement sizes from 3 m to 10 m (9.8 ft to 32.8 ft) the unit is simple and straightforward to set up using the onboard keypad and menu-led programming system.
Features
Compact and self-contained level measurement
Simple menu led setup
High power and narrow beam angles
High specification ATEX
Up to 10 m (32.8 ft) range available
Specifications
Dimensions | 186 mm H x 133 mm D (7.3 in H x 5.2 in D) |
Cable Entry | 2 x cable glands 4.5 mm to 10 mm (0.2 in to 0.4 in) (Torque to 2 NM) |
Mounting |
IMP3 - 3 m (9.8 ft) version: 1.5 in BSP/NPT IMP 6 - 6 m (19.7 ft) version: 1.5 in BSP/NPT IMP10 - 10 m (32.8 ft) version: 2 in BSP/NPT Suits BSP & NPT, parallel and tapered |
Weight | Nominal 1 kg (2.2 lb) |
Enclosure Protection | IP67 |
Temperature (Ambient) | -40 °C to +6 5 °C (-40 °F to +149 °F) |
Temperature (Process) | -40 °C to +80 °C (-40 °F to +176 °F) |
Input Voltage Range | 11-30 V, 3.5-22mA |
Accuracy | ±0.25% or 6 mm (0.2 in); whichever is greater |
Resolution | ±0.1% or 2 mm (0.1 in); whichever is greater |
4-20mA Outputs | Resolution 5 μA (both active and passive outputs) |
Temperature Compensation | Via internal temperature sensor (0.5 °C (± 32.9 °F) accuracy). Level and volume conversion are installed allowing linearisation for tank shapes. |
PC Interface | All parameters can be accessed and changed through PC Suite software. Echo traces may be viewed on-screen. |
Customer Service QQ
Customer Hotline:
Technical Supports