Products

current position:home page>Products>Electrical Instrument>Prostat>

PGT-61-164 SureTest® Circuit Analyzer

Updated:2024-05-30

Views:738

  • Brand: Prostat
  • Model: PGT-61-164
  • Description: Proper wiring is crucial to ensure safety and performance of Branch circuits. From a safety perspective, shock hazards and fires are mainly due to poor installation or failure of protective devices, s
  • Feedback
  • WeChat

    QQ

    Online Service

Product Details

PGT-61-164 SureTest® Circuit Analyzer Description:

Product Manual Datasheet Test & Measurement

Proper wiring is crucial to ensure safety and performance of Branch circuits. From a safety perspective, shock hazards and fires are mainly due to poor installation or failure of protective devices, such as GFCIs. From a performance perspective, electrical equipment and high-tech devices are found everywhere in residential and commercial buildings. They require reliable power to operate and function properly to ensure their longevity.

The unit is designed for 120 volts AC Hot Neutral and Ground only. It is protected in the event of a miswired outlet in the US electrical system to 240 VAC, but should be immediately unplugged and no tests performed until the voltage is corrected. Obviously that is not applicable in countries where the standard voltage is 240 H to N. The unit is not intended for nor is suitable for any other use than 120 VAC at 60 hertz.

Features

Designed for 120 Volts AC Hot Neutral and Ground

Measures Ground Impedance per ANSI/ESD S6.1

Neutral & Ground Wires Verification per ANSI/ESD S6.1

Verifies that Hot & Neutral are not reversed

Verifies that Hot & Equipment Ground are not reversed

Line Voltage

True RMS

Peak Voltage

Ground to neutral voltage

Frequency

Hot and neutral conductor impedances

Identifies false (bootleg) grounds

Tests GFCIs and EPDs for proper operation

Identifies proper wiring in 3-wire receptacles

Technical Specifications

Characteristics Ranges Resolution Basic Accuracy2
Line Voltage 85.0 - 265.0 VAC 0.1V 1.0% ± .2V
Peak Line Voltage 121.0 - 354.0 VAC 0.1V 1.0% ± .2V
Frequency 45.0 - 65.0 Hz 0.1Hz 1.0% ± .2Hz
% Voltage Drop 0.1% - 99.9% 0.1% 2.5% ± .2%
Voltage Loaded 10.0 - 132.0 VAC 0.1V 2.5% ± .2V
Neutral-Ground V 0.0 - 10.0 VAC 0.1V 2.5% ± .2V
Impedance - Hot 0.00 Ω - 3.00 Ω 0.01 Ω 2.5% ± .02 Ω
Neutral, & Ground > 3 Ω Unspecified
GFCI Trip Time 1mS to 6.500S counter 1 mS 1.0% ± 2mS
GFCI Trip Current 6.0 - 9.0 mA 0.1 mA 1.0% ± .2mA
EPD Trip Current 30.0 - 37.0 mA 0.1 mA 1.0% ± .2mA
Estimated Load on Line 1.00 – 20.0A 0.1A Unspecified
Characteristics
Display 128 x 64 OLED with backlight
Display update for Volt Less than 2.5 times Second
Over-range Indication on all functions Display “OL”
Operating Environment 32°F to 122°F (0°C to 50°C) at <80%RH
Storage Environment 32°F to 122°F (0°C to 50°C) at <80% RH
Altitude 6561.7 ft (2000m)
Case Construction ABS UL 94V/0/5VA rated
Dimensions (LxWxD) 6.4” x 3.0” x 1.4”
162mm x 76mm x 36mm
Weight 9.4 oz (267g)
Safety UL61010B-1, Cat III-300V
UL-1436 for AFCI, GFCI & Outlet
Warranty 2-year warranty

WeChat

Customer Service QQ

Customer Hotline:

010-52867770
0l0-52867771
l3811111452
l7896OO5796

Technical Supports

0l0-52867774
l7896OO5796
info@dorgean.com